Home · Science · Heat & Thermodynamics · Psychrometric Calculator
Psychrometric Calculator
The full state of a moist-air sample — humidity ratio, dew point, wet bulb, enthalpy and specific volume — from dry-bulb temperature, relative humidity and barometric pressure, by the ASHRAE formulations.
What this calculator does
The full state of a moist-air sample — humidity ratio, dew point, wet bulb, enthalpy and specific volume — from dry-bulb temperature, relative humidity and barometric pressure, by the ASHRAE formulations. Where a measure is involved, US and metric units are both accepted — flip the unit toggle and the figures convert with the same definitions the formula uses. Every result on this page is computed from the formula stated below, with no hidden rounding steps.
The formula and method
Psychrometric values follow the ASHRAE formulations: saturation pressure over water by the Magnus-Tetens correlation, humidity ratio from the partial pressure of vapour, and enthalpy of moist air per kilogram of dry air.
Barometric pressure defaults to standard sea-level pressure; at altitude, enter the local pressure for correct humidity ratios.
Results describe the state of the air sample only — no coil or load calculations are implied.
Worked example
With the example inputs this page opens with (dry-bulb temperature (°c) 25, relative humidity (%) 50, barometric pressure (kpa) 101.325), the result is 9.86 g/kg — humidity ratio (per kg of dry air). The full state of the air sample from its dry-bulb temperature, relative humidity and barometric pressure, by the ASHRAE formulations.
Quick reference
| Dry-bulb temperature (°C) | Humidity ratio (per kg of dry air) |
|---|---|
| 12.5 | 4.47 g/kg |
| 20 | 7.24 g/kg |
| 25 | 9.86 g/kg |
| 31.25 | 14.29 g/kg |
| 37.5 | 20.43 g/kg |
| 50 | 40.40 g/kg |
Computed with the same formulas as the calculator above — enter any values there for figures beyond this table.
Common questions
What is the humidity ratio?
The mass of water vapour carried by each kilogram of dry air. Unlike relative humidity it does not change when air is heated or cooled without adding or removing moisture, which is why HVAC engineers design with it.
Why does barometric pressure matter?
The humidity ratio is a pressure ratio at heart: at altitude the same temperature and relative humidity hold less water per kilogram of dry air, because the saturation vapour pressure is a larger share of a thinner atmosphere.
How does the Psychrometric Calculator work?
The full state of a moist-air sample — humidity ratio, dew point, wet bulb, enthalpy and specific volume — from dry-bulb temperature, relative humidity and barometric pressure, by the ASHRAE formulations. Dry-bulb temperature · Relative humidity · Pressure → Humidity ratio and full air state. The result updates as you type, and the formula and method on this page state the exact definitions used, so you can reproduce the calculation by hand.
What inputs does the Psychrometric Calculator need?
Dry-bulb temperature · Relative humidity · Pressure → Humidity ratio and full air state. Invalid entries — such as a zero denominator, an out-of-range value or a malformed list — produce a plain-language message instead of a misleading number.