Home · Science · Heat & Thermodynamics · Effectiveness-NTU Calculator

Effectiveness-NTU Calculator

Heat-exchanger effectiveness from the NTU method for a counterflow exchanger: ε = (1 − e^(−NTU(1−Cr)))/(1 − Cr·e^(−NTU(1−Cr))), plus the actual heat rate from q_max.

Your figures

Example result — edit the figures to make it yours

0.69

Effectiveness ε

Computed from the inputs on this page with the formula below — change any figure and every result updates.

Effectiveness ε69.08 %
Maximum possible heat rate30,000.00 W
Actual heat rate q20,723.56 W

What this calculator does

Heat-exchanger effectiveness from the NTU method for a counterflow exchanger: ε = (1 − e^(−NTU(1−Cr)))/(1 − Cr·e^(−NTU(1−Cr))), plus the actual heat rate from q_max. Where a measure is involved, US and metric units are both accepted — flip the unit toggle and the figures convert with the same definitions the formula uses. Every result on this page is computed from the formula stated below, with no hidden rounding steps.

The formula and method

ε = (1 − e^(−NTU(1−C_r))) / (1 − C_r·e^(−NTU(1−C_r))); q = ε · C_min · ΔT_max

The NTU method rates an exchanger without knowing its outlet temperatures. This tool uses the counterflow relation ε = (1 − e^(−NTU(1−Cr)))/(1 − Cr·e^(−NTU(1−Cr))), valid for Cr < 1.

NTU = UA/C_min and Cr = C_min/C_max. The actual heat rate is q = ε·q_max with q_max = C_min·(T_hot,in − T_cold,in). For Cr = 1 the counterflow limit is ε = NTU/(1+NTU); parallel-flow and other arrangements use different relations.

Worked example

With the example inputs this page opens with (number of transfer units ntu 1.5, capacity rate ratio c_r 0.5, minimum capacity rate c_min (w/k) 500, inlet temperature difference (k) 60), the result is 0.69 — effectiveness ε. Computed from the inputs on this page with the formula below — change any figure and every result updates.

Quick reference

Quick reference — varying number of transfer units ntu
Number of transfer units NTUEffectiveness ε
0.750.48
1.20.62
1.50.69
1.8750.76
2.250.81
30.87

Computed with the same formulas as the calculator above — enter any values there for figures beyond this table.

Common questions

Why use NTU instead of the log-mean temperature difference?

LMTD needs both outlet temperatures; when only inlets are known, LMTD forces iteration, while the NTU method gives the rating directly.

What happens as NTU grows large?

Effectiveness approaches 1 for a counterflow exchanger: the cold outlet can approach the hot inlet temperature, something a parallel-flow exchanger cannot do.

How does the Effectiveness-NTU Calculator work?

Heat-exchanger effectiveness from the NTU method for a counterflow exchanger: ε = (1 − e^(−NTU(1−Cr)))/(1 − Cr·e^(−NTU(1−Cr))), plus the actual heat rate from q_max. NTU · Capacity ratio · C_min · Max ΔT → Effectiveness and heat rate. The result updates as you type, and the formula and method on this page state the exact definitions used, so you can reproduce the calculation by hand.

What inputs does the Effectiveness-NTU Calculator need?

NTU · Capacity ratio · C_min · Max ΔT → Effectiveness and heat rate. Invalid entries — such as a zero denominator, an out-of-range value or a malformed list — produce a plain-language message instead of a misleading number.