Transformer Sizing Calculator

Size a transformer for a load: required kVA from kW and power factor, plus a headroom allowance for growth.

Your figures

Example result — edit the figures to make it yours

100 kVA

Required kVA

Computed from the inputs on this page with the formula below — change any figure and every result updates.

Sized kVA with headroom125.00 kVA
Line current at sized kVA180.42 A

What this calculator does

Size a transformer for a load: required kVA from kW and power factor, plus a headroom allowance for growth. Where a measure is involved, US and metric units are both accepted — flip the unit toggle and the figures convert with the same definitions the formula uses. Every result on this page is computed from the formula stated below, with no hidden rounding steps.

The formula and method

kVA = kW / pf, sized kVA = kVA × headroom factor

Headroom factor defaults to 1.25 (25% spare capacity).

Current output is three-phase line current at the entered voltage for the sized kVA.

Worked example

With the example inputs this page opens with (load (kw) 80, power factor 0.8, headroom factor 1.25, line voltage (v) 400), the result is 100.00 kVA — required kva. Computed from the inputs on this page with the formula below — change any figure and every result updates.

Quick reference

Quick reference — varying load (kw)
Load (kW)Required kVA
4050.00 kVA
6480.00 kVA
80100.00 kVA
100125.00 kVA
120150.00 kVA
160200.00 kVA

Computed with the same formulas as the calculator above — enter any values there for figures beyond this table.

Common questions

Why divide kW by power factor?

Transformers are limited by apparent power (kVA), which exceeds kW when pf < 1.

Is 25% headroom a rule?

It is a common planning allowance for load growth and harmonics, not a code mandate.

How does the Transformer Sizing Calculator work?

Size a transformer for a load: required kVA from kW and power factor, plus a headroom allowance for growth. Load kW · Power factor · Headroom → Required kVA. The result updates as you type, and the formula and method on this page state the exact definitions used, so you can reproduce the calculation by hand.

What inputs does the Transformer Sizing Calculator need?

Load kW · Power factor · Headroom → Required kVA. Invalid entries — such as a zero denominator, an out-of-range value or a malformed list — produce a plain-language message instead of a misleading number.