Home · Science · Electrical Engineering · 12 Volt Wire Size Calculator

12 Volt Wire Size Calculator

Sizes a copper conductor for a 12 V circuit so the voltage drop stays within an allowed percentage.

Your figures

Example result — edit the figures to make it yours

28

Required conductor area

Voltage drop at that area0.36 V
Nearest AWG (computed)2.8

What this calculator does

Sizes a copper conductor for a 12 V circuit so the voltage drop stays within an allowed percentage. Every figure on this page is computed from the formula or definition stated below, with no hidden rounding steps, and the method notes name the exact convention where more than one exists.

The formula and method

A = 2 × ρ × L × I ÷ (Allowed % × V), with ρ copper = 16.8 nΩ·m

The sizing is by voltage drop only, for a 12 V circuit: the conductor area that keeps the round-trip drop within the allowed percentage, using copper resistivity 16.8 nΩ·m at 20 °C.

Ampacity (heating) limits from wiring standards are a separate check and are not part of this formula — a complete installation design needs both. The AWG figure converts the area with the standard gauge relation.

Worked example

With the example inputs this page opens with (current (a) 20, one-way length (m) 15, allowed voltage drop (%) 3), the result is 28.00 — required conductor area. Change any figure and the result updates with the same formula.

Quick reference

Quick reference — varying current (a)
Current (A)Required conductor area
1014.00
1622.40
2028.00
2535.00
3042.00
4056.00

Computed with the same formulas as the calculator above — enter any values there for figures beyond this table.

Common questions

How does the 12 Volt Wire Size Calculator work?

Sizes a copper conductor for a 12 V circuit so the voltage drop stays within an allowed percentage. Current · One-way length · Allowed drop → Required conductor area. The result updates as you type, and the formula and method on this page state the exact definitions used, so you can reproduce the calculation by hand.

What inputs does the 12 Volt Wire Size Calculator need?

Current · One-way length · Allowed drop → Required conductor area. Invalid entries — such as a zero denominator, an out-of-range value or a malformed list — produce a plain-language message instead of a misleading number.

Is the 12 Volt Wire Size Calculator free to use?

Yes. It runs entirely in your browser with no sign-up, and the same calculator is available as an embeddable widget via the Embed button, so it can be placed on another site with its calculation intact.