Home · Construction & Home DIY · K-Factor Calculator

K-Factor Calculator

Sprinkler head discharge from its K-factor and the pressure at the head: the flow a sprinkler delivers in gallons per minute.

Your figures

Example result — edit the figures to make it yours

39.6

Discharge flow

What this calculator does

Sprinkler head discharge from its K-factor and the pressure at the head: the flow a sprinkler delivers in gallons per minute. Every figure is computed from the formula stated below. Densities, waste percentages and coverage rates appear as editable inputs with their planning defaults stated in the method notes — they are assumptions you can adjust to your supplier and your site, not industry standards.

The formula and method

Q = K·√P

Q is the discharge in US gallons per minute, K the sprinkler's listed K-factor and P the pressure at the head in psi.

K-factors are listed by the sprinkler manufacturer for each model and orifice size.

This is the head discharge only; pipe friction loss and system demand calculations are separate hydraulic steps.

Worked example

With the example inputs this page opens with (sprinkler k-factor 5.6, pressure at head (psi) 50), the result is 39.6 — discharge flow. Change any figure and the result updates with the same formula.

Quick reference

Quick reference — varying Pressure at head (psi)
Pressure at head (psi)Discharge flow
2025.043961
3030.672463
4035.41751
5039.59798
7548.497423
10056

Computed with the same formulas as the calculator above — enter any values there for figures beyond this table.

Common questions

Why does flow grow slowly with pressure?

Flow follows the square root of pressure: quadrupling the pressure only doubles the discharge. That is why pressure alone cannot fix an undersized head.

Where do I find the K-factor?

On the sprinkler's listing and data sheet — common values are 5.6 for standard 1/2 in heads and 8.0 for larger orifices.

How does the K-Factor Calculator work?

Sprinkler head discharge from its K-factor and the pressure at the head: the flow a sprinkler delivers in gallons per minute. K-factor · Pressure (psi) → Flow (gpm). The result updates as you type, and the formula and method on this page state every assumption used, so you can reproduce the calculation by hand.

What inputs does the K-Factor Calculator need?

K-factor · Pressure (psi) → Flow (gpm). Densities, waste percentages and coverage rates are editable — adjust them to your supplier's figures. Invalid entries produce a plain-language message instead of a misleading number.