Box Fill Calculator

Electrical box fill volume under NEC 314.16: the cubic inches your conductors, devices and grounds occupy in a box.

Your figures

Example result — edit the figures to make it yours

19.25

Required box volume

What this calculator does

Electrical box fill volume under NEC 314.16: the cubic inches your conductors, devices and grounds occupy in a box. Every figure is computed from the formula stated below. Densities, waste percentages and coverage rates appear as editable inputs with their planning defaults stated in the method notes — they are assumptions you can adjust to your supplier and your site, not industry standards.

The formula and method

Volume = Σ conductors × allowance + devices × 2 × device allowance + one allowance for the ground group

NEC 314.16 volume allowances per conductor: 14 AWG = 2.00 in³, 12 AWG = 2.25 in³, 10 AWG = 2.50 in³.

Each device (yoke) counts as two allowances of the largest conductor connected to it — pick that allowance in the device-wire field; the default 2.25 in³ corresponds to 12 AWG.

Simplification: the equipment-grounding group is counted as one allowance of the same device-wire size. Clamps, pigtails and other NEC details are outside this estimate; verify against the current NEC and local amendments.

Worked example

With the example inputs this page opens with (14 awg conductors 4, 12 awg conductors 2, 10 awg conductors 0, devices (switches/receptacles) 1), the result is 19.25 — required box volume. Change any figure and the result updates with the same formula.

Quick reference

Quick reference — varying 12 AWG conductors
12 AWG conductorsRequired box volume
014.75
219.25
423.75
628.25
832.75
1037.25

Computed with the same formulas as the calculator above — enter any values there for figures beyond this table.

Common questions

How do I use the result?

Choose a box whose marked volume (NEC Table 314.16(A)) is at least the required volume. If no volume is marked, the table's standard box sizes apply.

Do ground wires each count?

No. Under NEC 314.16 all equipment grounding conductors in the box together count as a single volume allowance, which is how the ground group is treated here.

How does the Box Fill Calculator work?

Electrical box fill volume under NEC 314.16: the cubic inches your conductors, devices and grounds occupy in a box. 14/12/10 AWG conductor counts · Devices · Grounds present → Required box volume (in³). The result updates as you type, and the formula and method on this page state every assumption used, so you can reproduce the calculation by hand.

What inputs does the Box Fill Calculator need?

14/12/10 AWG conductor counts · Devices · Grounds present → Required box volume (in³). Densities, waste percentages and coverage rates are editable — adjust them to your supplier's figures. Invalid entries produce a plain-language message instead of a misleading number.